27
Action ID
Increment counter #4 16387
Count operating time using counter #1
c
17408
Count operating time using counter #2
c
17409
Count operating time using counter #3
c
17410
Count operating time using counter #4
c
17411
c
This action converts a common event counter to the time counter which measures time at
0.1 hour resolution while the setpoint is in the operated state. Each time counter has a non-
volatile shadow counter which counts time at 1 second resolution before the corresponding time
counter is incremented.
5.10 Pulsing Setpoints
Table 5-20 Pulsing Registers
Setup registers (see Table 5-21)
2892-2893
Table 5-21 Pulsing Setup Registers
Parameter Offset Size,
byte
Direction Range
Output parameter ID +0 2 R/W see Table 5-22
Number of unit-hours per
pulse
+1 2 R/W 1-9999
Table 5-22 Pulsing Output Parameters
Pulsing parameter ID
None 0
kWh import 1
kWh export 2
kvarh import 4
kvarh export 5
kvarh total (absolute) 6
kVAh total 7
5.11 Relay Operation Control
These registers allow the user to manually override a relay operation that is normally operated
via alarm setpoints.
A relay allocated as a pulsing relay may not be manually operated or released. When a relay is
allocated for pulsing, it automatically reverts to normal operation.
Table 5-23 Relay Operation Control Registers
Parameter Address Size,
byte
Direction Range
Relay control status 3244 2 R/W see Table 5-24