Risk of electrocution!
Please adhere to the following points:
• The phase must be fused at the ampere value specified on the serial plate.
• It must be possible to disconnect the device from the mains power supply at all poles.
• The electrical system on the installation site must conform to IEC 364 (DIN VDE 0100). To
increase safety, the device should be connected to an RCD switch with 30 mA nominal er-
ror current (EN 61008). (Type B residual current circuit breakers ensure response even in
the event of smooth DC residual currents. This results in a high level of safety.)
• Never operate a device with a damaged power cable. Have a defective power cable or plug
replaced immediately by a qualified service technician.
• Schaerer AG recommends against using an extension cable. If an extension cable is used
despite this (minimum cross-section: 1.5 mm²), please comply with the manufacturer’s
specifications for the cable (operating instructions) and with locally applicable regulations.
• Route the power cable in such a way that it does not pose a tripping hazard. Do not pull
the cable over corners or sharp edges, pinch it between objects or allow it to hang loosely
in open spaces. Do not position the cable over hot objects, and protect the cable from ex-
posure to oil and aggressive cleaning products.
• Never lift or pull the device by the power cable. Never pull the plug out of the socket by its
cable. Never touch the power cable or plug with wet hands. Never insert a wet plug into a
power socket.
Power cable
Use of a faulty power cable or one that is not the original cable results in the risk of elec-
tric shock and fire.
Use the original power cable.
• The original power cable for your country can be obtained from your service partner.
• Power cables that are plugged in on both sides can be replaced by the customer.
• Permanently connected power cables must be replaced by a service technician.
Power requirements
Barista ONE
Mains Power requirements
Fuse protec-
tion (building
side)
Connecting
cable, conduc-
tor cross-sec-
tion
*1L, N, PE
(CH)
220 – 240 V ~ 50/60 Hz 2000-2400 W 10 – 16 A 3 x 1.0 mm²
1L, N, PE 100 V ~ 50/60 Hz 1350 W 15 A
3x1.5mm²
3 x 16 AWG
1L, N, PE 110 – 120 V ~ 50/60 Hz 1800 W 15 A
3x1.5mm²
3 x 16 AWG
2L, PE 200 V 2~ 50/60 Hz 1800 W 15 A
3x1.5mm²
3 x 16 AWG
2L, PE 220 – 240 V ~ 50/60 Hz 2000-2400 W 10 – 16 A 3 x 1 mm²