43
42
0.0~15.0%
P4-07
Default:
5.0
Torque upgrade
This parameter can make compensation for output voltage when
converter is running in a low frequency, so that the characteristics of low-
frequency torque which is controlled by V/F can be compensated and
upgraded.
If the setting of torque upgrade is too high, not only motor tends to be
overheated but also over current may be caused by it. In general, the setting
of torque upgrade must be no more than 10%. To prevent converter from over
current effectively, this parameter must be adjusted properly. This parameter
should be increased whenever there is heavy load; otherwise, please
decrease this parameter.
• The practical slip of motor varies from load to load. Output frequency can
be adjusted automatically according to the condition of loading by this
functional parameter, so that compensation can be made for the influence of
load on rotational speed of motor.
0.0~10.0Hz
P4-08
Default:
0.0Hz
Slip
compensation
• AVR function is also known as Automatic Voltage Regulation function.
Adjustment will be made automatically to stabilize output voltage whenever
there is fluctuation of input voltage, so that it can prevent converter from
overheat of motor caused by high output voltage or poor performance
caused by low output voltage.
P4-09
Default: 0
AVR
function
0 : Disabled
1 : always enabled
2 : only enabled in process of
deceleration
0:Disabled
1:Enabled
P4-10
Default: 0
Energy-efficient
running
• During the process of no-load or light-load running, output voltage can be adjusted
properly to achieve automatic energy conservation by detecting load current. This
parameter is applicable to the load of draught fan or pump.
• Multiple-phase V/F curves can be defined by these six parameters
above (P4-01~ P4-06)
The set value of V/F curves is generally set according to the load
characteristics of motor.
0.0Hz~P4-03 (Intermediate frequency 2)
0~ rated voltage (P3-00)
P4-01(Intermediate frequency 1)~P4-05
(Intermediate frequency)
0~ rated voltage (P3-01)
P4-03 (Intermediate frequency 2) ~
P3-00 (rated frequency)
0~ rated voltage (P3-01)
P4-01
Default:
1.0Hz
V/F Intermediate
frequency 1
P4-02
P4-03
P4-04
P4-05
P4-06
V/F Intermediate
voltage 1
V/F Intermediate
frequency 2
V/F Intermediate
voltage 2
V/F Intermediate
frequency 3
V/F Intermediate
voltage 3
Default:
5V
Default:
5.0Hz
Default:
25V
Default:
25.0Hz
Default:
115V
Precaution : motor may be overheated or even burned if preset low-
frequency voltage is too high, which may activate its over current protection.
V1<V2<V3, F1<F2<F3.
Voltage
V
Vb
V3
V2
V1
F1
F2
F3
Fb
Frequency Hz
5 : Self-adaptive control can be applied to running regulation by adapting itself to actual
load automatically, which is applicable to the operating situations which require greater
low-frequency torque as well as strict control on speed.
3 : high starting torque V/F is applicable to the operating situations which require higher
starting torque.
4 : Self-setting V/F indicates that V/F curve can be preset randomly by the functional
codes P4-01~P4-06, which is applicable to the operation with special load, for example
dewaterer or centrifuge, etc.
Parameters must be set correctly according to the information of nameplate on the motor
if this function needs to be enabled; it's only when the capacity of the motor is the same
as that of this converter can its performance be improved greatly.
P9-05
Overcurrent
stall gain
0–100 20
P9-06
Overcurrent
stall protective
current
100%–200% 150%
P9-07
Short-circuit to
ground upon
power-on
1
P9-08
Brake unit
action starting
voltage
200.0~2000.0V
P9-09
Fault auto
reset times
0〜20 0
P9-10
DO action
during fault
auto reset
0
P9-11
Fault auto
reset interval
0.1s〜100.0s 1.0s
P9-12
Input phase
loss protection
/contactor
energizing
protection
selection
11
P9-13
Output phase
loss protection
selection
0 : Disabled
1 : Enabled
1
P9-14
First failure
type
×
P9-15
Second failure
type
P9-16
Third
(most recent)
fault type
P9-17
Frequency at
the third failure
P9-18
Current at
the third fault
P9-19
Bus voltage at
the third fault
P9-20
Third fault input
terminal status
P9-21
Third fault
output
terminal status
P9-22
Inverter status
at the third fault
P9-23
Power-on time
during the
third fault
P9-24
Run time at
the third fault
P9-27
Frequency at
the second
failure
Parameter
Name
Setting Range
Default
Prope-
rty
Modbus
Address
Fun-
ction
Code
0 : Invalid
1 : Valid
0 : no act
1 : act
Ones place : Input phase loss
protection option
Tens place : Contactor suction
protection option
0: Disabled 1: Enabled
-
×
-
0 : no fault 1: Reserved
2 : accelerated overcurrent
3 : Deceleration over current
4 : Constant speed over current
5 : Accelerated overvoltage
6 : Deceleration overvoltage
7 : Constant speed overvoltage
8 : Buffer resistor overload
9 : Under voltage
10 : Inverter overload
11 : Motor overload
12 : Input phase loss
13 : Output phase loss
14 : Module overheating
15 : External fault
16 : Communication error
17 : Contactor abnormality
18 : Abnormal current detection
19 : Tuning error
20 : PG card is abnormal
21 : Parameter read & write error
22 : Inverter hardware is
abnormal
23 : Motor short circuit to ground
24 : Reserved
26 : Run time arrives
27 : User Defined Fault 1
28 : User-defined fault 2
29 : Power on time arrives
30 : Offload
31 : Loss of PID feedback at
runtime
40 : Fast current limit timeout
41 : Switching motor during
operation
42 : Speed deviation is too large
43 : Motor overspeed
45 : Motor overheating
51 : Initial position error
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
Modbus
Address
×
-
- -
×
- -
×
- -
×
- -
×
- -
×
- -
×
- -
×
- -
×
- -
×
User Manual
Chapter 5
User Manual
Chapter 5
○
○
○
○
○
○
○
○
○
63750
63751
63752
63753
63754
63755
63756
63757
63758
63759
63760
63761
63762
63763
63764
63765
63766
63767
63768
63769
63772
690