7 6 5 4 3 2 1 0
Parameter values = bit7×2 +bit6×2 +bit5×2 +bit4×2 +bit3×2 +bit2×2 +bit1×2 +bit0×2
7 6 5 4 3 2 1 0
=0×2 +1×2 +0×2 +0×2 +1×2 +0×2 +1×2 +0×2
=0+64+0+0+8+0+2+0
=74
Namely (01001010)2 = (74)10
Hence P8-17 should be set as 74
It’s mainly applied to the setting of Acc/Dec time for each program,
which is preset by binary mode (16 bit). Parameter can be entered only after
the binary value is converted into decimal value.
Take the following settings for example:
Parameter values= (0000000011100100) = (228)
2 10
Hence the P8-18should be set as 228
P9 : Protection Function parameters
These two parameters are mainly applied to the setting of real-
time relay protection of load motor. Effective thermal protection of motor
can be achieved by setting this parameter correctly when rated current of
motor is not matched with rated current of converter. Critical point of
overload protection (motor) = (allowed max. load current / rated current of
motor) * 100%
Timing for each
program's Acc-Dec
Default: 0
P8-18
0~65535
BIT 0~15 indicates the ACC/DEC
time of 0~7
Options for
overload protection
Default: 0
P9-00
0 : Disabled
1 : Enabled
Critical point of
overload protection
Default:
110%
P9-01
50~120%
0
12
3
4
5
6
7
8
9
10
1112
13
14
15
0 0 0 0 0 0 0 0 1 1 1 0 0 1 0 0
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
Acc/Dec Time 0 of Principal Frequency
Acc/Dec time 1 of first program
Acc/Dec time 2 of first program
Acc/Dec time 3 of first program
Acc/Dec time 0 of first program
Acc/Dec time 0 of first program
Acc/Dec time 0 of first program
Acc/Dec time 0 of first program
Weighted value
Binary set value
BIT
Over voltage protection function will be enabled so that the
decreasing output frequency of converter can be slowed down if bus voltage
detected by converter while running exceeds the critical point of over voltage
defined by parameter P9-03(in comparison with standard bus voltage); if it’s
detected that the bus voltage is lower than the critical point, converter will
continue to decelerate again.
Due to the influence of inertia load, actual droop rate of motor’s
rotational speed may be lower than droop rate of output frequency while
converter is decelerating; meanwhile, electrodes may feedback electric
energy to converter, which may raise the bus voltage of converter. If no action
is taken in time, stripping may be caused by over voltage of busbar.
Because of excessive load, actual rate of rotational speed rise of
motor may be lower than the rate of output frequency rise while converter is
decelerating; if no action is taken in time, stripping may be caused by over
current.
Over-current protection function will be enabled so that increasing
output frequency of converter can be slowed down if bus current detected by
converter while running exceeds the critical point of over current defined by
parameter P9-05; if it’s detected that output current is lower than the critical
point, converter will continue to accelerate again.
Phase-failure protection of input: options are selected to enable or disable
phase-failure protection for input Phase-failure protection of output: options
are selected to enable or disable phase-failure protection for output
Overload
protection
Default: 1
P9-02
0 : Disabled
1 : Enabled
Critical point of
Over voltage
Default:
118
P9-03
110.0~150.0%
Over current
protection
Default: 1
P9-04
0 : Disabled
1 : Enabled
Critical point of
over-current
Default:
180
P9-05
100~180%
Phase-failure
protection of input
Default: 0
P9-06
0 : Disabled
1 : Enabled
Phase-failure
protection of output
P9-07
0 : Disabled
1 : Enabled
Default: 0
61
60
Fun-
ction
Code
Parameter
Name
Setting range
Default
Prope-
rty
AC-14
AO1 target
voltage 2
6.000V 〜 9.999V
factory
reset
AC-15
AO1 measured
voltage 2
6.000V 〜 9.999V
AC-16
AO2 target
voltage 1
0.500V 〜 4.000V
AC-17
AO2 measured
voltage 1
0.500V 〜 4.000V
AC-18
AO2 target
voltage 2
6.000V 〜 9.999V
AC-19
AO2 measured
voltage 2
6.000V 〜 9.999V
Modbus
Address
factory
reset
factory
reset
factory
reset
factory
reset
factory
reset
AC-20
AI2 measured
current 1
0.000mA 〜 20.000mA
AC-21
AI2 sampling
current 1
0.000mA 〜 20.000mA
AC-22
AI2 measured
current 2
0.000mA 〜 20.000mA
AC-23
AI2 sampling
current 2
0.000mA 〜 20.000mA
AC-24
AO1 ideal
current 1
0.000mA 〜 20.000mA
AC-25
AO1 measured
current 1
0.000mA 〜 20.000mA
AC-26
AO1 ideal
current 2
0.000mA 〜 20.000mA
AC-27
AO1 measured
current 2
0.000mA 〜 20.000mA
factory
reset
factory
reset
factory
reset
factory
reset
factory
reset
factory
reset
factory
reset
factory
reset
5-2 Monitoring parameter
U0 Group Basic monitoring parameter
Fun-
ction
Code
Parameter
Name
Display range
Instruction
U0-00
Running
frequency
0.01~320.00Hz
Display operating frequency
and set frequency (Hz)
U0-01
Set frequency
U0-02
Bus voltage
0.0~3000.0V
Display bus voltage (V)
U0-03
Output voltage
0~1140V
Display inverter output voltage
(V)
U0-04
Output current
0.0~6553.5A
Display inverter output current
(A)
U0-05
Output Power
0~32767kW
Display inverter output power
(kW)
U0-06
Output torque
-200.0~200.0%
Display inverter output torque
during operation
U0-07
Input terminal
status
0~32767
Input status: X1~X9
corresponds to Bit0~Bit8
U0-08
Output terminal
status
0~1023
Output terminal status: Y2,
relay,
U0-09
AI1 voltage
0.01V
Y1 corresponds to Bit0, Bit1,
Bit3
U0-10
AI2 voltage
0.01V
Display input AI1 voltage (V)
U0-11
AI3 voltage
0.01V
Display input AI2 voltage (V)
U0-12
Count value
0~65535
Display input AI3 voltage (V)
U0-13
Length value
0~65535
Display count value
U0-14
Load speed
display
0~65535
Display length value
U0-15
PID setting
0~65535
Display load speed
U0-16
PID feedback
value
0~65535
Display PID settings
U0-17
PLC stage
0~16
Display PLC operation phase
User Manual
Chapter 5
User Manual
Chapter 5
○
○
○
○
○
○
44047
44048
44049
44050
44051
44052
28673
28674
28675
28676
28677
28678
28679
28680
28681
28682
28683
28684
28685
28686
28687
28688
28689
28690
Modbus
Address
-10.00V 〜 +10.00V
-10.00V 〜 +10.00V
-10.00V 〜 +10.00V
-10.00V 〜 +10.00V
-10.00V 〜 +10.00V
-10.00V 〜 +10.00V