Compact & Powerful
VFD Series

Table of Contents

Questions and Answers:

Selec VFD Series Specifications

General IconGeneral
BrandSelec
ModelVFD Series
CategoryDC Drives
LanguageEnglish

Summary

Preface

Safety Precautions

1.1 Warning

Critical safety warnings and immediate precautions.

1.2 Safety guidelines

General guidelines for safe operation, wiring, and maintenance.

Installation

2.1 Installation environment

Specifies suitable environmental conditions for installation.

2.2 Installation instructions and space limit

Details installation procedures and required clearances.

Wiring

3-2 Standard Wiring Diagram

Illustrates the standard electrical connection diagram for the VFD.

3-3 Description of Terminals

Explains the function and purpose of each terminal.

Detailed Explanation of Functional Parameters

P0- Basic Parameters

Detailed explanations for fundamental functional parameters P0.

P1- Keypad Parameters

Detailed explanations for keypad configuration parameters P1.

Fault Handling And Troubleshooting

7.1 Malfunction and solutions

Lists common malfunctions, their causes, and possible solutions.

Safety Precautions

1.1 Warning

Critical warnings regarding electrical shock and safe practices.

1.2 Safety guidelines

Essential safety rules to follow during operation and maintenance.

1.3 Delivery and Installation

Procedures for checking the device upon delivery and initial installation.

Installation

2.1 Installation environment

Specifies suitable environmental conditions for installation.

2.2 Installation instructions and space limit

Details installation procedures and required clearances.

WIRING

3-2 Standard Wiring Diagram

Provides the standard electrical wiring diagram for connections.

3-3 Description of Terminals

Explains the function and purpose of each terminal.

Standard Wiring Diagram

Default Settings

Default settings for control circuit connections.

Potentiometer

Wiring for potentiometer input.

Description of Terminals

3-3-1 Connection of Input Power Terminals

Details on connecting input power terminals.

3-3-2 Connection of Output Power Terminals

Details on connecting output power terminals.

3-3-4 Earth terminal PE

Instructions for grounding the PE terminal.

Explanations of control loop terminals

Analog Input Terminals (Al1, Al2)

Terminals for analog signal inputs.

Control Terminals (GND, +V)

Terminals for control signal grounding and power.

Keyboard and Panel

4.1 Illustration of Keypad

Visual representation of the VFD's keypad layout.

4.2 Units LEDs descriptions

Explanation of the unit indicator LEDs.

4.3 Function LEDs descriptions

Explanation of the function indicator LEDs.

Keys Description

ESC Key

Function of the ESC key for navigation and exiting.

PRG Key

Function of the PRG key for programming and saving.

RUNSTP Key

Function of the RUN/STP key for starting, stopping, and resetting.

Illustrations of keyboard operations

RUNNING

5-1 Commissioning

Steps for initial setup and verification before operation.

5-1-3 Quick Commissioning

A streamlined process for initial VFD setup.

Quick Commissioning

SPECIFICATIONS OF FUNCTIONAL PARAMETERS

6-1 Functional Parameters Table

A comprehensive table detailing all functional parameters.

P0- BASIC FUNCTIONAL PARAMETERS

Details of basic functional parameters from P0.

KEYPAD PARAMETERS

P1-00 Default startup display parameter

Sets the default display parameter upon startup.

P1-01 Selection of display information

Selects which information is displayed on the pages.

P1-02 Password Disable

Option to disable the password protection feature.

START AND STOP PARAMETERS

P2-00 Start mode

Defines the method for starting the VFD.

P2-05 Stop mode

Defines the method for stopping the VFD.

MOTOR PARAMETERS

P3-00 Rated frequency

Sets the rated frequency of the motor.

SCALAR CONTROL PARAMETERS

P4-00 Vf curve setting

Configures the V/f curve for scalar control.

P4-01 VF Intermediate Frequency 1 (F1)

Sets the first intermediate frequency point for the V/f curve.

INPUT FUNCTION PARAMETERS

P5-00 Lower Limit OF AI1

Sets the lower limit for the analog input Al1.

P5-01 Corresponding Setting of AI1 Lower Limit

Maps the Al1 lower limit to a set frequency.

INPUT FUNCTION PARAMETERS

P5-06 Lower Limit OF AI2

Sets the lower limit for the analog input Al2.

P5-12 PNPNPN Selection

Selects the input type for multifunction inputs.

P5-13 Multifunction Input X1

Configures the function for multifunction input X1.

OUTPUT FUNCTION PARAMETERS

P6-01 Relay Output Options

Configures the behavior of relay output options.

PI CONTROL PARAMETERS

P7-00 PI reference source

Selects the reference source for the PI control loop.

P7-01 PI set value

Sets the target value for the PI control loop.

PI CONTROL PARAMETERS

P7-04 Proportional gain

Sets the proportional gain for the PI controller.

P7-05 Integral time

Sets the integral time for the PI controller.

SIMPLE PLC AND MULTISPEED OPTIONS

P8-00 Program run mode

Defines how the Simple PLC program will run.

PROTECTION PARAMETERS

P9-00 Overload protection enable

Enables or disables overload protection.

P9-01 Critical value of Overload protection

Sets the threshold for overload protection.

P9-02 Overload detection time

Sets the time delay for overload detection.

PROTECTION PARAMETERS

P9-12 Undervoltage protection enable

Enables or disables undervoltage protection.

P9-18 Overcurrent protection enable

Enables or disables overcurrent protection.

FAULT HISTORY

PA-00 Previous fault code

Displays the code of the most recent fault.

COMMUNICATION PARAMETERS

Pb-00 Slave Address

Sets the unique address for the VFD on the communication bus.

Pb-01 Modbus Data Format

Configures the data format for Modbus communication.

ENHANCED PARAMETERS

PC-00 Acc. time 1

Sets the first acceleration time.

PC-01 Dec. time 1

Sets the first deceleration time.

PC-08 Hopping Frequency 1 Lower Limit

Sets the lower limit for hopping frequency band 1.

Detailed Explanation of Functional Parameters

P0: Basic parameters

Detailed explanations for fundamental functional parameters P0.

Frequency setting

Acc. time 0

Dec. time 0

Default running direction

Anti-reversion setting

Max Frequency

Upper limiting frequency

Lower limiting frequency

Keypad Parameters

P1-00 Default startup display parameter

Sets the default display parameter upon startup.

P1-01 Selection of display information

Selects which information is displayed on the pages.

P1-02 Password Disable

Option to disable the password protection feature.

Frequency Switch Source

Reference Frequency

Start and Stop Parameters

P2-00 Start mode

Defines the method for starting the VFD.

START AND STOP PARAMETERS

P2-01 Starting Frequency

Sets the frequency at which the motor starts.

P2-02 Retention time for starting

Sets the time for magnetic flux formation during starting.

P2-05 Stop mode

Defines the method for stopping the VFD.

START AND STOP PARAMETERS

P2-06 Start frequency of DC braking

Sets the start frequency for DC braking.

START AND STOP PARAMETERS

P2-07 Braking current for stopping

Sets the braking current for stopping the motor.

P2-08 Braking time for stopping

Sets the duration for braking current application.

P2-10 Deadtime between FWDREV

Sets the time delay when switching rotation direction.

Lower frequency limit crossing action

Hibernation Restore Delay Time

Motor Parameters

P3-00 Rated frequency

Sets the rated frequency of the motor.

P3-01 Rated Voltage

Sets the rated voltage of the motor.

P3-02 Rated Current

Sets the rated current of the motor.

Scalar Control Parameters

P4-00 Vf curve setting

Configures the V/f curve for scalar control.

Scalar Control Parameters

P4-01 VF Intermediate Frequency 1 (F1)

Sets the first intermediate frequency point for the V/f curve.

P4-02 VF Intermediate Voltage 1

Sets the voltage for the first intermediate frequency point.

P4-03 VF Intermediate Frequency 2(F2)

Sets the second intermediate frequency point for the V/f curve.

Torque boost

AVR Function

Energy-efficient running (EER)

Input Function Parameters

P5-00 Lower Limit OF AI1

Sets the lower limit for the analog input Al1.

P5-01 Corresponding Setting of AI1 Lower Limit

Maps the Al1 lower limit to a set frequency.

Input Function Parameters

P5-06 Lower Limit OF AI2

Sets the lower limit for the analog input Al2.

P5-12 PNPNPN Selection

Selects the input type for multifunction inputs.

P5-13 Multifunction Input X1

Configures the function for multifunction input X1.

Input Function Parameters

P5-14 Multifunction Input X2

Configures the function for multifunction input X2.

P5-15 Multifunction Input X3

Configures the function for multifunction input X3.

P5-16 Multifunction Input X4

Configures the function for multifunction input X4.

Input Function Parameters

Set Value 7 Forward Jog

Assigns Forward Jog function to an input.

Set Value 9 Increase Frequency

Assigns Increase Frequency function to an input.

Set Value 11 Acc-Dec Time Option 1 (A1)

Assigns Acc-Dec Time Option 1 to an input.

Terminal Control Mode

0: Two-Wire Control Mode 1

Configures two-wire control mode 1.

1: Two-Wire Control Mode 2

Configures two-wire control mode 2.

Terminal Filtering Time

Terminal Frequency update Step Size

Output Function Terminals

P6-00 Relay Output Options

Configures the behavior of relay output options.

Set Value 1 Running

Sets output terminal to indicate Running condition.

Set Value 3 Fault Output

Sets output terminal to indicate a fault condition.

PI Control Parameters

P7-00 PI reference source

Selects the reference source for the PI control loop.

P7-01 PI set value

Sets the target value for the PI control loop.

P7-02 Feedback source

Selects the source for the feedback signal in PI control.

PI Control Parameters

P7-04 Proportional gain

Sets the proportional gain for the PI controller.

P7-05 Integral time

Sets the integral time for the PI controller.

P7-06 Deviation limit

Sets the deviation limit for PI control stability.

PI Control Parameters

P7-07 Sampling Time

Sets the sampling period for feedback quantity.

P7-08 Feedback disconnection value

Defines the value for detecting feedback disconnection.

Simple PLC and Multispeed parameters

P8-00 Program run mode

Defines how the Simple PLC program will run.

P8-01 First phase speed

Sets the speed for the first phase of the PLC program.

P8-08 The runtime of principal frequency

Sets the runtime for the principal frequency in PLC.

Simple PLC and Multispeed parameters

P8-16 Time unit of multivelocity

Sets the time unit for multispeed settings.

P8-17 Running direction of programs

Defines the running direction for PLC program phases.

Acc-Dec Time for each phase

PROTECTION PARAMETERS

P9-00 Overload protection enable

Enables or disables overload protection.

P9-01 Critical value of Overload protection

Sets the threshold for overload protection.

P9-02 Overload detection time

Sets the time delay for overload detection.

PROTECTION PARAMETERS

P9-06 Overvoltage protection enable

Enables or disables overvoltage protection.

P9-12 Undervoltage protection enable

Enables or disables undervoltage protection.

PROTECTION PARAMETERS

P9-18 Overcurrent protection enable

Enables or disables overcurrent protection.

P9-24 Undercurrent protection enable

Enables or disables undercurrent protection.

P9-30 Automatic Current Limit

Enables or disables automatic current limiting.

FAULT HISTORY

PA-00 Previous fault code

Displays the code of the most recent fault.

COMMUNICATION PARAMETERS

Pb-00 Slave Address

Sets the unique address for the VFD on the communication bus.

Pb-01 Modbus Data Format

Configures the data format for Modbus communication.

ENHANCED PARAMETERS

PC-00 Acc. time 1

Sets the first acceleration time.

PC-01 Dec. time 1

Sets the first deceleration time.

PC-06 Jog Acc. Time

Sets acceleration time for jogging operation.

ENHANCED PARAMETERS

PC-12 FDT Level Detection Value

Sets the detection value for FDT level.

PC-13 FDT Level Lagged Value

Sets the lagged value for FDT level detection.

ENHANCED PARAMETERS

PC-14 Amplitude of Frequency Arrival

Indicates when the drive is approaching the set frequency.

PC-15 Setting Count

Sets the target count value for counting pulses.

PC-16 Specific Count

Sets the specific count value for signaling.

FAULT HANDLING AND TROUBLESHOOTING

7.1 Malfunction and solutions

Lists common malfunctions, their causes, and possible solutions.

Fault Code 1 Overvoltage fault

Overvoltage fault causes and solutions.

Fault Code 2 Under-voltage fault

Undervoltage fault causes and solutions.

Fault Code 3 Over-current fault

Overcurrent fault causes and solutions.

FAULT HANDLING AND TROUBLESHOOTING

7.1 Malfunction and solutions

Lists common malfunctions, their causes, and possible solutions.

Fault Code 9 External Communication failure

External communication failure causes and solutions.

Fault Code 11 Pl fault

PI fault causes and solutions.

7.2. Common Faults and processing schemes

Discusses common faults and their resolution.

MAINTENANCE

8.1. General maintenance and upkeep

Guidelines for routine inspection and general maintenance procedures.

8.2. Inspection and replacing damaged parts

Procedures for inspecting and replacing worn components.

Storage

Product Warranty

EXTERNAL COMMUNICATION

9.1. Protocol Content

Information on the content and structure of the communication protocol.

9.2. Protocol Instructions

Instructions for using the communication protocol.

Frame Structure

Standard Structure of RTU Frame

Details the standard structure of RTU communication frames.

Command code and data description

9.4.1 Format of No.1 address for Setting

Describes the command format for setting parameters.

9.4.2 Format of No.1 address for reading

Describes the command format for reading parameters.

CRC Mode

Read-write rules of parameter address for function code

9.5.1 Monitoring Parameters

Parameters available for monitoring via communication.

9.5.2 Commanding the drive over communication

Commands for controlling the drive via communication interface.

9.5.3 Drive status

Information on the current status of the drive.

APPENDIX

10.1 Technical Specifications

Detailed technical specifications of the VFD.

Technical Specifications

Protection Functions

Lists the protection functions available on the VFD.

Display

Details about the VFD's display type and parameters.

External comm.

Specifications for external communication protocols.

Product Dimensions

Product Code

Identifies the product code and associated dimensions.