24
User Manual
P9-13
Critical value of Under-
voltage protection
85 % to 99 % 90 %
Yes
40913
P9-14
Undervoltage trip time
0.1 to 999.9 s 0.1 s
Yes
40914
P9-15
Undervoltage pre-alarm
enable
0: Disabled; 1: Enabled
0
No
40915
P9-16
Undervoltage pre-alarm
detection level
P9-13 to 100% 95 %
No
40916
P9-17
Undervoltage pre-alarm
detection time
0.1 to 999.9 s 0.1s
No
40917
P9-18
Overcurrent protection
enable
0: Disabled; 1: Enabled
1
Yes
40918
P9-19
Critical value of
Overcurrent protection
100 to 180 % 120 %
Yes
40919
P9-23
Overcurrent pre-alarm
detection time
0.1 to 999.9 s 0.1 s
No
40923
P9-24
Undercurrent protection
enable
0: Disabled; 1: Enabled
0
Yes
40924
P9-25
Critical value of UC
protection
20 % to 90 % 25 %
Yes
40925
P9-26
UC trip time
0.1 to 999.9 s 0.1 s
Yes
40926
P9-27
UC pre-alarm enable
0: Disabled; 1: Enabled
0
No
40927
P9-28
UC pre-alarm detection
level
P9-25 to 90 % 50 %
No
40928
P9-29
UC pre-alarm detection
time
0.1 to 999.9 s 0.1 s
No
40929
P9-30
Automatic Current Limit
0: Disabled; 1: Enabled
0
Yes
40930
P9-31
Automatic Current
Limit Level
50 – 180 % 150 %
No
40931
P9-20
Overcurrent trip time
0.1 to 999.9 s 0.1 s
Yes
40920
P9-21
Overcurrent pre-alarm
enable
0: Disabled; 1: Enabled
0
No
40921
P9-22
Overcurrent pre-alarm
detection level
100 to P9-19
105 %
No
40922