23
User Manual
P8-14
Sixth phase time
0.0
No
40814
P8-15
Seventh phase
time
0.0
No
40815
P8-16
Time unit of
multi-velocity
0: Seconds; 1: Minutes
2: Hours
0
No
40816
P8-17
Running direction
of programs
0-255 BIT0-7 indicates
directions
for 0-7 (0:FWD 1:REV)
0
No
40817
P8-18
Acc Time for
0-3 phase
0-255 BIT0-7 indicates Acc
times for 0-3 (0:FWD 1:REV)
0
No
40818
P8-19
Dec time for
4-7 phase
0-255 BIT0-7 indicates Dec
times for 4-7 (0:FWD 1:REV)
0
No
40819
0.0-999.9
0.0-999.9
Fun.
Code
Description Settings and Range
Default
Value
Basic
Setting
Modifi-
cation
M-bus
Address
P9- PROTECTION PARAMETERS
P9-00
Overload
protection enable
0: Disable; 1: Enable
1
Yes
40900
P9-01
Critical value of
Overload protection
50 – 120 % 120 %
Yes
40901
P9-02
Overload detection time
0.1 to 999.9 s 0.1 s
Yes
40902
P9-03
Overload pre-alarm
enabled
0: Disabled; 1: Enabled
0
No
40903
P9-04
Overload pre-
alarm detection level
50 – P9:01
110 %
No
40904
P9-05
Overload pre-alarm
detection time
0.1 to 999.9 s 0.1 s
No
40905
P9-06
Overvoltage protection
enable
0: Disabled; 1: Enabled
1
Yes
40906
P9-07
Critical value of OV
protection
101 % - 115 % 110 %
Yes
40907
P9-08
Overvoltage Trip time
0.1 to 999.9 s 0.1 s
Yes
40908
P9-09
Overvoltage pre-alarm
enable
0: Disabled; 1: Enabled
0
No
40909
P9-10
Overvoltage pre-alarm
detection level
100% to Critical value
of OV protection
(P9-07)
105 %
No
40910
Fun.
Code
Description Settings and Range
Default
Value
Basic
Setting
Modifi-
cation
M-bus
Address
P9-11
Overvoltage pre-alarm
detection time
0.1 to 999.9 s 0.1 s
No
40911
P9-12
Undervoltage protection
enable
0: Disabled; 1: Enabled
1
Yes
40912