PA- FAULT HISTORY
PA-00
Previous fault code
0-20 0
Yes
× 41000
PA-01
2nd to previous fault code
0-20 0
Yes
× 41001
PA-02
3rd to previous fault code
0-20 0
Yes
× 41002
PA-03
Previous fault operating
frequency
- -
No
× 41003
PA-04
Previous fault Current
- -
No
× 41004
PA-05
Previous fault bus voltage
- -
No
× 41005
PA-06
Previous fault input state
- -
No
× 41006
PA-07
Previous fault output state
- -
No
× 41007
-
Fun.
Code
Description Settings and Range
Default
Value
Basic
Setting
Modifi-
cation
M-bus
Address
PB- COMMUNICATION PARAMETERS
PB-00
Slave Address
1-127
1
Yes
41100
PB-01
Modbus Data
Format
0: 8-N-1; 1: 8-N-2; 2: 8-E-1
3: 8-E-2; 4: 8-O-1; 5: 8-O-2
0
Yes
41101
PB-02
Response Delay
0- 200ms
20ms
No
41102
PB-03
Serial Timeout
0: Disable; 1: Time Setting
0
No
41103
PB-04
Serial Timeout
Time Setting
0.1- 60.0s
5.0s
No
41104
PB-05
Abnormal Action
Selection
0: Warn & Continue Operation
1: Continue Operation Without
Warning; 2: Alarm Shutdown
(Coast to Stop);
3: Alarm Shutdown
(Ramp to Stop)
0
No
41105