P0-03
Frequency
setting
Lower limiting Frequency (P0-10)
-Upper limiting Frequency (P0-09)
Default : 50.0 Hz
This function reflects the set frequency. When using external communication, this parameter needs
to be updated for updating the drive’s set frequency.
P0-04 Acc. time 0 0.1 s – 999.9 s
Default : 10.0 s
P0-05 Dec. time 0 0.1 s – 999.9 s
Default : 10.0 s
Acceleration and Deceleration times are defined as the time the drive will take to accelerate from
0.0Hz to Max Running Frequency (P0-08) and from Max Running Frequency (P0-08) to 0.0 Hz
respectively. For intermediate frequencies, the acceleration and deceleration times will vary
accordingly.
Time
Stop signal
Run signal
Output freq.
Max freq.
Set feq.
Actual
Acc Time
Actual
Dec Time
Time
Preset Acc time
Preset Dec time
28
User Manual
P0-06
Default running
direction
0: Standard direction
1: Reverse direction
Default : 0
This parameter is used to determine the default running direction of the drive. It is useful when there
is a need to permanently change the default direction of the motor. It helps the user as they do not
need to manipulate the wiring to change the default direction. The direction chosen here will be
treated as FORWARD (FWD) for all drive operations.