P2-07
Braking current for
stopping
0 - 150 % Default : 50 %
P2-08
Braking time for
stopping
0.0 – 50.0 s
Default : 0.0 s
Similar to starting operation, the braking current for stopping is a percentage of the motor rated
current and determines the magnitude of the braking current that will be injected into the motor during
stopping. The P2-08 parameter determines the duration for which this current is applied.
Before applying the braking current, in high inertia loads, it becomes important to allow the motor to
demagnetize itself. This is done to protect the motor from drawing excessive amounts of current and
damaging itself. The duration specified here is applicable post the drive has reached the P2-06
frequency and before the DC injection current is applied.
P2-09
Demagnetizing time
0.0 – 30.0 s
Default : 0.1 s
34
User Manual
P2-10
Deadtime between
FWD/REV
0.0 – 50.0 s
Default : 0.2 s
This parameter determines the transient time for which the drive will be at 0.0Hz when switching
direction.
FWD/REV Dead time
Output
frequency
FWD/REV dead
time