Lower frequency
limit crossing action
0: Running with low Limit
Frequency
1: Stopping
2: Standby
3: Hibernation
Default : 0
P2-12
Hibernation Restore
Delay Time
Delay Time 0 – 50.0 s
Default : 0.0 s
However, to get out of hibernation, the set frequency needs to be above the lower limiting frequency
for a usersettable duration as determined in the parameter P2-12.
3: The drive enters hibernation mode. This is similar to standby mode as the drive turns all output
switches OFF.
1: The drive initiates stopping action
This setting is used to determine the drive’s operation in cases where the set frequency goes below
the lower
0: The drive continues running with Lower Limiting frequency as the set
frequency
limiting frequency as set in P0-10.
2: The drive enters standby mode. Here, the drive output remains in OFF condition till the set
frequency goes above the lower limiting frequency
35
User Manual
Hibernation
Set frequency
Lower limit of
frequency
O/P frequency
Lower limit of
frequency
Hibernation
time delay