P8-16
Time unit of
multivelocity
0: Seconds ; 1: Minutes
2: Hours
Default : 0
The P8-16 parameter defines the time unit that will be used for the time settings in P8-08 to P8-15
Frequency (Hz)
P8-01
P8-02
P8-03
P8-03
P8-05
P8-06
P8-07
P8-08 P8-09 P8-10 P8-11
P8-12 P8-13 P8-14 P8-15
FWD
REV
Time (t)
P8-04
50
User Manual
P8-17
Running direction
of programs
0-255 BIT0-7 indicates directions
for 0-7 (0:FWD 1:REV)
Default : 0
The P8-17 parameter determines the direction that will be followed for the individual phases in the
simple PLC program.
Weighted value
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
Direction (example)
1
1
0
1
0 0
1
0
Bit No.
7
6
5
4
3
2
1
0
Phase No.
7 6
5
4
3
2 1
0
Each bit in the byte corresponds to the corresponding phase in the simple PLC program as shown in
the table above.
A value 0 in the bit corresponds to a FWD direction rotation while writing a value 1 to the bit will
cause REV direction rotation.
In the above example, we have phases 0 (principal frequency), 2, 3, and 5 running in the forward
direction while
phases 1, 4, 6, and 7 will run in the reverse direction. The parameter value comes out to be
1 4 6 7
2 +2 +2 +2
i.e. 210.