22 English
Stand pipe temperature sensor isn’t connected or has a malfunction.
Mixing valve opens.
TABLE: Resistance values for temperature sensors type Pt-1000
Temp. [°C] Resist. [Ω] Temp. [°C] Resist. [Ω] Temp. [°C] Resist. [Ω] Temp. [°C] Widerst. [Ω]
-20 922 35 1136 90 1347 145 1555
-15 941 40 1155 95 1366 150 1573
-10 961 45 1175 100 1385 155 1592
-5 980 50 1194 105 1404 160 1611
0 1000 55 1213 110 1423 165 1629
5 1020 60 1232 115 1442 170 1648
10 1039 65 1252 120 1461 175 1666
15 1058 70 1271 125 1480 180 1685
20 1078 75 1290 130 1498 185 1703
25 1097 80 1309 135 1515 190 1722
30 1117 85 1328 140 1536 195 1740
OPERATION MODE BY SENSOR FAILURE
In the menu there are software tools to help with setting the controller.
Restoring the controller settings are made through the selection of:
RESET OF ALL CONTROLLER PARAMETERS
Restores all settings of parameters P1, S1 (except S1.1) and S2.
RESET OF ALL CONTROLLER SETTINGS AND RESTART INITIAL SETUP
Restores all parameters to default values and starts the initial setup.
SAVE USER‘S SETTINGS
Save current parameter values as user‘s settings.
LOAD USER‘S SETTINGS
Load previously saved user‘s settings.
Before performing of the commands stated above, the controller requires a
conrmation of the selected command.
FACTORY SETTINGS