4.4.4 Programming of the analogue output (if option)
Or
To the menu RELAY.
Choice of the limitation type on the output:
Std: output between 0 (mA or V) and 110%
of the programmed value (dS.OUt or
FS.OUt).
Max: 22 mA or 11 V
SCALE: Output limited to the programmed
dS.OUt and FS.OUt values.
*
p13
AnA
AnA
tYpe
Out. I
Out. U
Ds.OUt
00.00
Fs.OUt
DO.dIS
t
FO.dIS
00.00
00.00
00.00
LIN
SCALE
Std.
Indication of the output type
(current or voltage).
Setting of the analogue output
down and up scale:
00.00 < x < 22.00 (mA)
00.00 < x < 11.00 (V)
Display corresponding to the
output down scale.
Down
Up
Display corresponding to the
output up scale.
* The return values (for sensor break or error self-diagnosis)
will not take the limitation of the output into account.