33
Ŷ General specifications
Data storage: By non-volatile memory (EEPROM)
Ɣ Operating ambient
Ambient temperature: -10–50°C
Humidity range: Below 90%RH (no condensation)
Derating from 50°C
Storage temperature: -20–65°C
Over voltage category: ll
Elevation: Max. 2000 m
Pollution class: 2 (IEC 60664)
Supply voltage: 100–240 V AC ± 10% (50/60 Hz)
Ɣ Power consumption: 10 VA
Ɣ Input noise removal ratio: Normal mode: 50 dB or above (50/60 Hz)
Common mode: 120 dB or above (50/60 Hz)
Ɣ Common mode: 120 dB or above (50/60 Hz)
Ɣ Applicable standard: Safety: IEC61010-1 and EN61010-1
IEC61010-2-030 and EN61010-2-030
EMC: EN61326-1
Ɣ Power supply
short-break time: Within 50 ms, normal action continuation (when 200V)
Ɣ Insulation resistance: Input-output terminal and power terminal interval, 500 V DC, 20Mȍ or above
Ɣ Dielectric strength: Input-output terminal and power terminal interval, 2300 V AC, 1 min.
Ɣ Material of case: Resin mold (UL94V-1 equivalent)
Ɣ External dimensions: SRS1: H48 × W48 × D66 mm, panel depth: 62 mm
SRS3: H96 × W96 × D69 mm, panel depth: 65 mm
SRS4: H96 × W48 × D66 mm, panel depth: 62 mm
SRS5: H48 × W96 × D66 mm, panel depth: 62 mm
Ɣ Mounting: Panel flush mounting
Ɣ Applicable panel thickness: 1.0–3.5 mm
Ɣ Panel cutout: SRS1: H45 × W45 mm
SRS3: H92 × W92 mm
SRS4: H92 × W45 mm
SRS5: H45 × W92 mm
Ɣ Weight: SRS1: Approx. 100 g
SRS3: Approx. 190 g
SRS4: Approx. 120 g
SRS5: Approx. 120 g