7. Measuring range codes
Select measuring range from the following table.
Note: Changing the code initializes all data related to measuring range. Change setting after switching
to reset mode from the 0-1 screen.
Input type Code Measuring range (°C) Measuring range (
;
)
Multi-input
Thermocouple
B *6 hi *1 0
1800°C 0
3300 ;
R hj -50
1700°C 0
3100 ;
S hk 0
1700°C 0
3100 ;
K
hl *2 -199.9
400.0°C -300
750 ;
hm 0
1370°C 0
2500 ;
E hn *2 0
700°C 0
1300 ;
J ho *2 -200
600°C -320
1100 ;
T *6 hp *2 -270
400°C -450
750 ;
N hq 0
1300°C 0
2300 ;
PL ll *3 ih 0
1300°C 0
2300 ;
WRe5-26 ii 0
2300°C 0
4200 ;
U *3 ij *2 -199.9
400.0°C -300
750 ;
L ik 0
600°C 0
1100 ;
Kelvin
K il *4 10.0
350.0K
AuFe-C
r
im *5 0.0
350.0K
RTD Pt100 kl -199.9
300.0°C -300
600 ;
mV -10–50 mV oj
Scaling range: -1999
9999 digit
Span: 9999 digit
*1 Thermocouple B: Accuracy guarantee is not applicable to 400°C (750°F) or below.
*2 Thermocouple K (Celsius, Fahrenheit), E, J, T, U:
Accuracy of indicated values below -100°C and -148°F is ± (1.5%FS + 1 digit).
*3 Thermocouple PL ll, U: Accuracy of indicated values is ± (1.5%FS + 1 digit + 1°C).
*4 Thermocouple K (Kelvin) accuracy temperature range:
10.0–30.0K: ±(2.0%FS + 1 digit + 1K) Provided the wire resistance is 10ȍ or below
31.0–70.0K: ±(1.5%FS + 1 digit + 1K) Provided the wire resistance is 10ȍ or below
71.0–350.0K: ±(1.0%FS + 1 digit + 1K)
*5 Thermocouple AuFe-Cr: Accuracy of indicated values is ± (1.0%FS + 1K).
*6 Thermocouple B, T:
Accuracy of indicated values below these temperatures is subject to wire resistance 50ȍ or below:
B: 500°C (930°F)
T: -240°C (-400°F)
*7 Temperatures below -273°C (-459°F) are subject to scaleover display.
*8 With or without a decimal point is selectable for TC and Pt.
Note: Unless otherwise designated, the factory default settings are as follows:
Input range Standard/rating Measuring range
Multi-input Thermocouple K 0
1370°C