www.Siargo.com MF5806E1 User Manual 24 | Page
Alarm: Flow rate upper
limited
0x0098 ~ 0x0099
Set alarm value for an upper flow rate limit
Alarm values = Value (0x0098)*65536 + Value (0x0099)
When the flow rate is above a set
value, an alarm will be triggered.
Note: need to disable the write protection.
Alarm: Flow rate lower
limit
0x009A ~ 0x009B
Set alarm value for a lower flow rate limit
Alarm values = Value (0x009A)*65536 + Value (0x009B)
When the flow rate
is below a set value, an alarm will be triggered.
Note: need to disable the write protection.
0x00AE ~ 0x00AF
Change the default password
Password values = Value (0x00AE)*65536 + Value (0x00AF)
Available: 00000 ~ 99999
Note: need to disable the write protection.
0x00F0
Reset or calibrate the offset
UINT 16, Fixed value 0xAA55
To reset or calibrate the offset, write 0xAA55 to register 0x0027.
Note: When you execute this function, make sure there is NO flow in
the flow channel.
Note: need to disable the write protection.
Reset accumulated
flow rate
0x00F2
Reset the accumulated or totalized flow rate value
UINT 16, Fixed value 0x0001
To reset the accumulated or totalized flow rate value, write 0x0001 to register
0x00F2.
Note: need to disable the write protection.