5 TROUBLESHOOTING
58
OPERATING INSTRUCTIONS | AFS60/AFM60 PROFINET 8015078/1EF3/2021-12-13 | SICK STEGMANN
Subject to change without notice
Subindex .1 Sensor status (S_STAT-B)
Bit
Designation
Description
15
INVALID_PARA_SENS_EEP
Memory error caused by invalid checksum on
reading the EEPROM during encoder initialization:
In the area of the sensor configuration data
14
INVALID_ARA_DEV_CONFIG
In the area of the device configuration data
13
INVALID_DIAG_PROC_B
In the area of the diagnostics of the basic
process data
12
INVALID_DIAG_SERV_A
In the area of the diagnostics of the service
data
11
INVALID_PARA_COMM_X
In the area of the user configuration,
communication mapping
10
Reserved
9
Reserved
8
INVALID_PARA_BAS
In the area of the user configuration, basic
parameters
7
Reserved
6
Reserved
5
FREQUENCY_WARN
Warning, speed exceeds configured maximum
value
4
INVALID_PRESET_OPER
Warning, triggered on executing the preset
function. The preset value is outside the measuring
range (CMR).
3
Reserved
2
Reserved
1
INVALID_PARAM_BAS
Warning, occurred on changing or writing
parameter values:
In the area of the encoder profile specific
objects
0
Reserved
Table 45: Subindex .1 Sensor status (S_STAT-B)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK AFS/AFM60 PROFINET and is the answer not in the manual?

SICK AFS/AFM60 PROFINET Specifications

General IconGeneral
BrandSICK
ModelAFS/AFM60 PROFINET
CategoryMedia Converter
LanguageEnglish

Related product manuals