12 Technical data
12.1 Data sheet
Table 10: General system data
Minimum Typical Maximum
Protective field height, depending on
t
ype
300mm to 2,100mm, 150-mm steps
Resolution (detection capability),
dependin
g on type
14mm or 30mm
Protective field width
1)
2)
3)
Resolution 14mm 0m...8m 0m…10m
Resolution 30mm 0m…12m 0m…15m
Protection class
4)
III (IEC 61140)
Enclosure rating IP65 (IEC60529)
IP67 (IE
C 60529)
5)
Supply voltage U
V
a
t the device
6)
7)
8)
19.2V 24V 28.8V
Residual ripple
9)
±10%
Synchronization Optical
Type Type 4 (IEC61496-1)
Category Category 4 (ISO 13849-1)
Performance level
10)
PL e (ISO 13849–1)
Safety integrity level
10)
SIL 3 (IEC 61508)
SIL claim limit
10)
SILCL 3 (IEC62061)
PFH
D
(me
an probability of a danger‐
ous failure per hour)
3.7 × 10
-9
T
M
(mis
sion time) 20years (ISO 13849-1)
Safe status when a fault occurs At least one OSSD is in the OFF state.
Power-up delay of sender and
r
eceiver after supply voltage is
applied
2s
Equipment group/category II
XII3G
, XII3D
Labeling according to
IE
C/EC60079‑0, IEC/EC60079‑7,
IEC/EC60079‑28 for 3G and
IEC/EC60079‑0, IEC/EC60079‑31
for 3D
X II 3G Ex ec op is IIC T4 Gc
X II 3D Ex t
c IIIC T135°C Dc
0°C < Ta < +55°C
Specific operating conditions X
11)
Intended areas of use Zone 2, Zone 22
1)
If the protective fields are very wide, there is a possibility that all four alignment quality LEDs will not light
up e
ven when alignment is excellent.
2)
The minimum scanning range specifies a range in which a function is guaranteed to operate correctly
and safely under industrial conditions. A sufficient level of signal reserve to ensure very high availability is
included in the calculation.
3)
The typical scanning range specifies a range in which the safety light curtain operates correctly and safely
under industrial conditions. The level of signal reserve is enough to ensure high availability.
4)
SELV/PELV safety extra-low voltage.
5)
IP*7 is not approved for explosion-hazardous areas.
6)
The external voltage supply must be capable of bridging a brief power failure of 20ms as specified in
IEC60204-1. Suitable power supply units are available as accessories from SICK.
7)
A fuse rated maximum 4A shall be installed in the 24VDC power supply circuit to the device in order to
limit the available current.
8)
The nominal voltage in explosion-hazardous areas is 24VDC.
TECHNICAL DATA 12
8021796/1DCM/2022-10-27 | SICK O P E R A T I N G I N S T R U C T I O N S | deTec4 Core Ex II 3GD
57