7.3.3.5 Alarm
The alarm output can be configured via the switching function for Q1 and Q2.
For a detailed functional description, see "Non-safety-related functions", page 20.
Function Description
Alarm In Alarm switching mode, the switching threshold is automatically
defined based on the measuring capability of the device. In this case,
the switching output behavior can be manually selected.
Switching behavior With the Q1 output behavior setting, you can manually select whether
the signal level warning output is Active high or Active low.
Example alarm parameterization for Q1:
1. Connect to the device and switch to the Outputs settings page in SOPASET.
2. Set the Q1 switching function to Alarm.
3. Set the Q1 output behavior according to the desired function: Active low
4. Transfer parameters the device using the “Write all parameters” button.
5. Check whether the function works appropriately for the configured parameters!
7.3.3.6 Analog output
If the 4mA … 20mA setting is selected, output 2 functions as an analog current
output. The measured value of the device is output as a proportional-linear current
value that corresponds to the other device settings. Increasing (safety-related) and
decreasing (non-safety-related) scaling is possible.
The necessary settings can either be taught-in or set manually. These are described in
the following.
For a detailed functional description, see "Safety-related functions", page 16 and "Non-
safety-related functions", page 20.
NOTE
The analog output has a resolution of 12bits.
Depending on whether the larger distance value is taught in for 4mA or for 20mA, the
analog output behavior is either “increasing” (distance for 4mA <distance for 20mA)
or “decreasing” (distance for 4mA > distance for 20mA).
Increasing scaling of the analog output (safety-related function)
COMMISSIONING AND CONFIGURATION 7
8027663//2022-08-04 | SICK O P E R A T I N G I N S T R U C T I O N S | DT35S
37
Subject to change without notice