Decreasing scaling of the analog output (non-safety-related function)
Setting Description
4mA
With the 4mA setting, the distance value to
be output with 4mA at the analog output
can be set manually in millimeters.
The Teach function can be used to teach in
for the 4mA … 20mA output function the
current distance value for an analog output
of 4mA for the measured value.
20mA
With the 20mA setting, the distance value to
be output with 20mA at the analog output
can be set manually in millimeters.
The Teach function can be used to teach in
for the 4mA … 20mA output function the
current distance value for an analog output
of 20mA for the measured value.
Example analog output parameterization for Q2:
1. Connect to the device and switch to the Outputs settings page in SOPASET.
2. Set the Q2 switching function to 4mA ... 20mA.
3. Enter the distance to switching point1 in the input window (optional: position the
object at switching point1 and perform a Teach ).
2)
4. Enter the distance to switching point2 in the input window (optional: position the
object at switching point2 and perform a Teach ).
2)
5. Transfer parameters the device using the “Write all parameters” button.
6. Check whether the function works appropriately for the configured parameters!
2)
For a decreasing behavior, the distance for 20mA must be smaller than the distance for 4mA.
7 COMMISSIONING AND CONFIGURATION
38
O P E R A T I N G I N S T R U C T I O N S | DT35S 8027663//2022-08-04 | SICK