01.202038/45 H39.ELEKS014EN-00
GENIUS 2.2 PANIC, Electromechanical mul-point lock
If an oponal access control system (e.g. a ngerprint
scanner) is to be installed in combinaon with the
GENIUS 2.2 PANIC, refer to the relevant instrucons for
informaon about commissioning and tesng.
If the lever handle/ the push bar does not return to its
original posion by itself, there is a malfuncon.
f
Check the routed pocket for dimensional accuracy.
f
Check that the lever handle/ the push bar is correct-
ly seated.
f
Check that the door hardware is correctly seated.
If the lever handle does not return to its original posi-
on by itself, the mul-point lock must be checked by
KFV.
f
If you cannot remove the key, dismount the prole
cylinder and check it for malfuncon.
f
If the prole cylinder does not funcon faultlessly,
replace the cylinder and repeat the test step.
If the prole cylinder funcons faultlessly, there is a
mechanical disorder in the mul-point lock.
If the GENIUS 2.2 PANIC does not move to the locking
posion, check the funcon of the magnec sensor. To
do this, open the door and hold a magnet to the mag-
nec sensor (see chapter 4.2 and ).
f
The magnec eld sensor is working correctly if the
GENIUS 2.2 moves to the locking posion. Check the
posion of the magnet and the airgap and adjust
this according to the specicaon (3.5 mm+- 1.5
mm).
f
Then carry out a manual adjustment of the magnet-
ic sensor (see chapter 8.6).
If due to a block movement, the GENIUS 2.2 PANIC
does not move completely to the locking posion, an
acousc error signal will sound and the status LED will
ash red.
f
Check whether the locking elements run smoothly
into the frame parts. If this is not the case, adjust
the frame parts.
In accordance with DIN EN 179 and DIN EN 1125, the
acvang forces must be recorded and documented for
the inial installaon.
Verwenden Sie hierfür das „Prüf- und Wartungs-Pro-
tokoll“ aus der Bedienungsanleitung.