Description   
3.4 Structure 
  1FT7 synchronous motors 
20  Operating Instructions, 04/2010, 610.40075.40b 
Water cooling 
The motor can only be operated in a closed cooling-water circuit with a cooling unit. The 
motor is connected to the cooling circuit by means of two female threads at the rear of the 
motor. The inlet and outlet connections can be freely selected. 
Table 3- 5  Technical data relating to water cooling 
Cooling water connection  G1/4" 
1FT706x  3 l/min 
1FT708x  4 l/min 
Cooling water flow 
1FT710x  5 l/min 
Max. pressure at inlet  Max. 6 bar  
1FT706x  < 0.3 bar for minimum cooling water flow 
1FT708x  < 0.3 bar for minimum cooling water flow 
Pressure drop between inlet and outlet 
1FT710x  < 0.25 bar for minimum cooling water flow 
Minimum cooling water inlet temperature  T
cooling
 > T
ambient
 - 5 K 
Maximum cooling water inlet temperature, without 
derating 
≤ 30 °C, higher values will cause derating 
Only water with an appropriate quantity of additives to protect against corrosion and 
minimize the growth of algae can be used as a coolant. Other coolants (e.g. cooling-
lubricating medium, water-oil mixtures with 10% oil and higher) may result in derating. 
If there is a risk of frost, preventive measures must be taken during operation, storage, and 
transportation (anti-freeze, emptying the cooling circuit and blowing it out with air, etc.). Use 
and concentration of the anti-freeze according to information provided by the manufacturer. 
Different anti-freeze agents should not be mixed. 
A filter (100 µm) must be installed in the inlet pipe to protect the motor against 
contamination. Pipes and valves can be made out of brass, stainless steel, or plastic. 
However, if different materials are used in close proximity to one another, then the insulation 
rating must be taken into account, which is why zinc must not be used in cooling circuits. 
If a restrictor is needed to limit the flow of coolant, it is best to install it downstream of the 
motor. It must not be installed directly in front of the inlet because the effects of cavitation 
may damage the motor. 
The values specified for the cooling water correspond to the requirements for a closed 
cooling circuit. Not all of the specified concentrations will occur in the cooling water at the 
same time.