Function test interval for 3RM11/3RM13 Failsafe motor starters 
In continuous operation, the key safety values apply in the case of a function test interval 
(state change of the outputs) ≤ 1 year. 
•  Actuate the connected sensors. 
•  Check their effect on the safe evaluation unit and the downstream actuators. 
•  Activate the safe evaluation unit via the connected sensors. 
•  Check their effect on the safe evaluation unit and the downstream actuators. 
•  Defective devices must be replaced. 
 
 
Bypassing the safety function in the event of a fault in the case of 3RM11/3RM13 Failsafe 
motor starters with 110 to 230 V AC
110 V DC control supply voltage 
The control signal for the control inputs in the case of 3RM11/3RM13 Failsafe motor 
starters with 110 to 230 V AC control supply voltage must come from A1. Otherwise, the 
safety function is bypassed in the event of a fault. Thus, only relay outputs are admissible 
when using a PLC.  
Do not use a separate control voltage. Only use the relay outputs when using a PLC. 
 
 
Bypassing the safety function when using device connectors 
When operating with a 3SK1 safety relay and a device connector, the supply voltage for 
3RM1 motor starters is established via the device connectors. 
In this case, do not connect anything to terminals A1 and A2 of the 3RM1 motor starters, in 
order to prevent bypassing of the safety function. 
 
 
Failure of the safety function during hybrid operation of Failsafe and Standard motor 
starters 
Hybrid operation of 3RM10/3RM12 Standard motor starters with 3RM11/3RM13 Failsafe 
motor starters in safety-related applications is not admissible. 
Only ever use safety-related motor starters (3RM11 Failsafe and 3RM13 Failsafe) in safety-
related applications.