Typical circuits   
A.1 Typical circuits for 3RM1 Standard 
  SIRIUS 3RM1 motor starter 
146  Manual, 11/2013, A5E0345285095020A/RS-AB/002 
Direct-on-line starter 24 V DC with switch operation and single-phase motor 
The current is drawn via only one phase. The motor is connected at T3. The second 
connection is directly at the neutral conductor. On the 3RM1 motor starter, T1 is wired direct 
with T2, and L2 direct with L3. 
 
 
Connection IN2 on reversing starters must not be used in the case of single-phase motors. 
 
 
Damage from operating capacitive loads 
When using capacitive loads, the switching components in the 3RM1 motor starter can be 
damaged by excessively high making currents. 
Do not operate capacitive loads such as frequency converters on the 3RM1 motor starter. 
Operation of single-phase capacitor motors is admissible. 
In this operating mode, switching on and off is carried out only with connection IN1.