Switching the 3RM1 motor starter under normal operating conditions 
A typical application area of the 3RM1 motor starter is the switching and protection of 
motors. You can also operate the 3RM1 motor starter on resistive loads such as heaters. 
 
 
Minimum loads must be observed for the 3RM1 motor starters.  
You will find additional information in the chapter "Minimum load current (Page 57)". 
 
 
Damage from operating capacitive loads 
When using capacitive loads, the switching components in the 3RM1 motor starter can be 
damaged by excessively high making currents. 
Do not operate capacitive loads such as frequency converters on the 3RM1 motor starter. 
Operation of single-phase capacitor motors is admissible. 
 
 
Damage during operation on non-sinusoidal voltages 
When operating frequency converters, the switching components in the 3RM1 motor starter 
can be damaged by non-sinusoidal voltages. 
Do not operate the 3RM1 motor starter on outputs of frequency converters. 
 
Direct-on-line starter 
Using the 3RM1 motor starter as a direct-on-line starter  
All 3RM1 motor starters can be used as direct-on-line starters. 
To switch the 3RM1 motor starter on, apply the control voltage at input IN1. 
After the motor is switched off, the motor starter accepts a new start after 500 ms. 
You can also use the versions of the 3RM1 motor starter with a rated operational current up 
to 7 A for switching resistive loads up to I
AC51
 = 10 A under normal operating conditions.