Configuration 
  4.2 Ambient conditions 
SIRIUS 3RM1 motor starter 
Manual, 11/2013, A5E0345285095020A/RS-AB/002 
57 
Permissible operating voltage 
To be able to ensure safe isolation of the circuits from each other in accordance with IEC 
60947-1, the following operating voltages are permissible:  
Table 4- 1  Safe isolation of the 3RM1 motor starters 
... to ... 
Control circuit  
(A1/A2, OUT, IN1-3,  
M1/M2)
Signaling contacts  
(98/95/96)
Main circuit 
(1L1/3L2/5L3 
2T1/4T2/6T3)
Control circuit  
(A1/A2, OUT, IN1-3,  
M1/M2)
Signaling contacts  
(98/95/96)
Main circuit 
(1L1/3L2/5L3 
2T1/4T2/6T3)
The minimum load current is 20% of the set motor current, but at least the absolute minimum 
current specified in the tables below. 
The minimum load current differs in the case of Standard 3RM10/3RM12 and Failsafe 
3RM11/3RM13 motor starters:  
Table 4- 2  Minimum load current in the case of Standard 3RM10/3RM12 motor starters 
Motorized load  0.05 A  0.14 A  0.6 A 
Resistive load  0.05 A  0.14 A  0.6 A 
 
Table 4- 3  Minimum load current in the case of Failsafe 3RM11/3RM13 motor starters 
Motorized load  0.05 A  0.14 A  0.6 A 
Resistive load  0.25 A  1 A  3.5 A 
As soon as the minimum current limit is violated, fault detection (phase failure) picks up.