C-11
TP27, TP37 Equipment Manual
Release 01/00
Remedy:CauseMessage
681 Overload caused by too many variables (setpoints/actual
values).
Fault in connection between the OP and PLC.
Check the interface parameters.
682 Incorrect interface parameters configured. Configure fewer process links for the
screen displayed.
683 Configuration error:
upper limit = lower limit
Correct the limits and retransfer configura-
tion.
684 Non-existent trend switch buffer requested. Check PLC program/OP configuration.
Only use trend request area 2 for trends
with switch buffer.
701 Internal error
Incorrect assignment of “head –> res“ when receiving
variable.
702 Job can not be executed. Change interface or configure area pointer.
703 Flash memory full. Restrict the configuration.
704 Incorrect CPU specified under ”PLC –> Parameters”. Change configuration and retransfer.
706 Recipe request will not be processed as another request is
already active.
722 Internal error
Incorrect mailbox type received (OP15 –> OP5)
723 Internal error
OP5: more than 500 messages are specified in the area
pointer lists.
Change area pointer list.
724 Internal error
Mailbox type not implemented.
771 Internal error
Error during communication (→ messages).
779 Internal error
Internal error during MPI download; possibly due to
buffer problems.
Reset and repeat MPI download.
780 Internal error
Undefined error from communication with PLC.
781 An ”Online Setter” function has been incorrectly defined
in ProTool.
S
stem Messa
es