7SG15 MicroTAPP Settings
©2012 Siemens Protection Devices Limited Chapter 3 Page 6 of 8
8 Output Config Menu
SETTING RANGE DEFAULT
Relay Healthy C RL 1 to RL 5 (to RL 13) NONE
Tap Raise C RL 1 to RL 5 (to RL 13) RL 5
Tap Lower C RL 1 to RL 5 (to RL 13) RL 4
Tap-changer Runaway * C RL 1 to RL 5 (to RL 13) RL 2
Operation Permitted C RL 1 to RL 5 (to RL 13) NONE
Volt Control Alarm C RL 1 to RL 5 (to RL 13) NONE
U/V O/V Alarm C RL 1 to RL 5 (to RL 13) RL 3
Overload Alarm C RL 1 to RL 5 (to RL 13) RL 3
Control in Auto C RL 1 to RL 5 (to RL 13) NONE
Control in Local C RL 1 to RL 5 (to RL 13) NONE
Ready for Switch-out C RL 1 to RL 5 (to RL 13) RL 1
Tap Incomplete * C RL 1 to RL 5 (to RL 13) RL 2
Tap Count Alarm C RL 1 to RL 5 (to RL 13) NONE
Sum of I^2 Alarm C RL 1 to RL 5 (to RL 13) NONE
Block Raise Command C RL 1 to RL 5 (to RL 13) NONE
Block Lower Command C RL 1 to RL 5 (to RL 13) NONE
VT Fuse Blown C RL 1 to RL 5 (to RL 13) NONE
Remote VT fuse blown C RL 1 to RL 5 (to RL 13) NONE
Tap-change Reset C RL 1 to RL 5 (to RL 13) NONE
[102] Dead Reckoning Block C RL 1 to RL 5 (to RL 13) NONE
MPPC Failure C RL 1 to RL 5 (to RL 13) NONE
End of Tap Range C RL 1 to RL 5 (to RL 13) NONE
Tap not achievable C RL 1 to RL 5 (to RL 13) NONE
[102] Volt. Target Ackn. C RL 1 to RL 5 (to RL 13) NONE
Group 1 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 2 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 3 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 4 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 5 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 6 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 7 Selected C RL 1 to RL 5 (to RL 13) NONE
Group 8 Selected C RL 1 to RL 5 (to RL 13) NONE
NOTE: the available settings in this Menu will be dependant upon the number of hardware output relays
fitted.
* These operations also result in a Lockout.