7SG15 MicroTAPP Settings
©2012 Siemens Protection Devices Limited Chapter 3 Page 7 of 8
9 Status Config Menu
SETTING RANGE DEFAULT
Inverted Inputs C S1 to S11 (to S19) NONE
MicroTAPP Enable C S1 to S11 (to S19) SI 1
Raise from T/C C S1 to S11 (to S19) SI 2
Lower from T/C C S1 to S11 (to S19) SI 3
Tap in Progress C S1 to S11 (to S19) SI 7
Tap Raise Block C S1 to S11 (to S19) NONE
Tap Lower Block C S1 to S11 (to S19) NONE
Prepare Switch-out C S1 to S11 (to S19) SI 6
Tap Stagger C S1 to S11 (to S19) NONE
Remote Raise * C S1 to S11 (to S19) SI 10
Remote Lower * C S1 to S11 (to S19) SI 11
Remote Auto * C S1 to S11 (to S19) SI 8
Remote Manual * C S1 to S11 (to S19) SI 9
Select Aux Target 1 C S1 to S11 (to S19) SI 4
Select Aux Target 2 C S1 to S11 (to S19) SI 5
Select Aux Target 3 C S1 to S11 (to S19) NONE
Local / Remote C S1 to S11 (to S19) NONE
[102] Volt. Target Incr. * C S1 to S11 (to S19) NONE
[102] Volt. Target Decr. * C S1 to S11 (to S19) NONE
[102] Volt. Target Reset * C S1 to S11 (to S19) NONE
Select Group 1 ** C S1 to S11 (to S19) NONE
Select Group 2 ** C S1 to S11 (to S19) NONE
Select Group 3 ** C S1 to S11 (to S19) NONE
Select Group 4 ** C S1 to S11 (to S19) NONE
Select Group 5 ** C S1 to S11 (to S19) NONE
Select Group 6 ** C S1 to S11 (to S19) NONE
Select Group 7 ** C S1 to S11 (to S19) NONE
Select Group 8 ** C S1 to S11 (to S19) NONE
NOTE: the available settings in this Menu will be dependant upon the number of hardware status inputs
fitted.
* These inputs are positive edge triggered. All other inputs are level dependant.
** These operations may be configured as edge or level triggered.