7SG15 MicroTAPP Application Guide
9.1 Voltage Transformers
Either a 3 phase or single phase voltage transformers can be used for voltage measurement. A 3 phase VT is
preferable so that the level and voltage quality of all phases can be monitored. Figure 10 shows the relay
connections for a 3 phase VT.
Where a single phase VT is used it can be connected between phases or from phase to earth, in either case the
MicroTAPP set-up menu for the transformer allows the particular connection to be specified. Figure 11 shows the
connections for a single phase VT.
9.2 Current Transformers
Figures 10 and 11 also show the relay connections for a current transformer. The input allows for any CT nominal
secondary current up to 5 amps to be used. The MicroTAPP setup menu for the transformer allows the particular
ratio to be specified.