7SR224 Argus Performance Specification
2.10 51G Time Delayed Measured Earth Fault
2.10.1 Reference
Parameter Value
Is
Setting 0.005, 0.006 …0.100, 0.105… 1.0 xIn
Char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Manufacturer specific curves
See ‘Performance Specification Appendix 1’
Tm
Time Multiplier setting 0.025, 0.05… 1.6
t
d
Delay setting (DTL) 0, 0.01… 20 s
t
res
Reset setting ANSI DECAYING, 0, 1… 60 s
IDMTL 2 to 20 xIs
I
Applied current (for
operate time)
DTL 5 xIs
2.10.2 Operate and Reset Level
Attribute Value
I
op
Operate level
105 % Is, ± 4 % or ± 1% In
Reset level
≥ 95 % I
op
Repeatability
± 1 %
-10 °C to +55 °C
≤ 5 %
Variation
f
nom
- 3 Hz to f
nom
+ 2 Hz
≤ 5 %