7SR224 Argus Performance Specification
2.11 51SEF Time Delayed Sensitive Earth Fault
2.11.1 Reference
Parameter Value
Is
Setting 0.005, 0.006 …0.100, 0.105… 1.0 xIn
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Manufacturer specific curves
See ‘Performance Specification Appendix 1’
Tm
Time multiplier 1.0
t
d
Delay setting 0.00…20.00 s
t
res
Reset setting DECAYING, 0, 1…60 s
IDMTL 2 to 20 xIs
I
Applied current (for
operate time)
DTL 5 xIs
2.11.2 Operate and Reset Level
Attribute Value
I
op
Operate level
105 % Is, ± 4 % or ± 1% In
Reset level
95 % I
op
± 4 % or ± 1% In
Repeatability
± 1 %
-10 °C to +55 °C
5 %
Variation
f
nom
- 3 Hz
to f
nom
+ 2 Hz
harmonics to f
cutoff
5 %
©2010 Siemens Protection Devices Limited Chapter 3 Page 33 of 49