EasyManua.ls Logo

Siemens 7SR224 - Inverse Time Overcurrent (51 C)

Siemens 7SR224
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR224 Argus Commissioning & Maintenance Guide
©2010 Siemens Protection Devices Limited Chapter 6 Page 22 of 73
1
1
General Starter
51-n
51c-n Setting
51c-n Charact
51c-n Time Mult
51c-n Follower DTL
c
51c-n Reset
Cold Load
Enabled
L1 Dir En
L2 Dir En
L3 Dir En
Disabled
c
start
trip
c
start
trip
c
start
trip
51c-n Min. Operate Time
Reduced
Current
Enabled
Disabled
51c-n Delay (DTL)
CB Open
CB Closed
Pick-up Time
Drop-off Time
Reduced Current DTL
Reduced
Current Level
c
<
<
<
IL1
IL2
IL3
51c
See Delayed
Overcurrent
(51-n)
1
&
S
R
Q
&
Figure 2-5 Cold Load Logic diagram
Ensure that the Cold load active is not raised. This can be reset by CB closed for more than the Cold Load Drop-
off Time or current less than the Reduced Current Level for greater than the Reduced Current Time. Check the
Cold Load Pick-up Delay by applying or simulating CB Open. Measure the time delay before Cold Load Active is
raised. Apply current above the Reduced Current Level if this functionality is Enabled before applying CB Closed.
Measure the time for Cold Load Active to reset.
2.4.1 Inverse Time Overcurrent (51C)
It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the
Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function.
Gradually increase current until Pickup LED operates.
Apply 2x setting current and record operating time,
Apply 5x setting current and record operating time.
Compare to calculated values for operating times
Operate Current Operate Time
Ph. Dir Char.
(NI EI VI
LTI, DTL)
Is
(A)
TM
P.U.
(Amps)
D.O.
(Amps)
2 x Is
(sec)
5 x Is
(sec)
NOTES
I
L1
(I
A
)
I
L2
(I
B
)
P.U.
D.O.
&
TIMING
TESTS
I
L3
(I
C
)

Table of Contents

Other manuals for Siemens 7SR224

Related product manuals