EasyManua.ls Logo

Siemens 7SR224 - Environmental Performance; General; Emissions

Siemens 7SR224
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR224 Argus Performance Specification
1.4 Environmental Performance
1.4.1 General
1.4.1.1 Temperature
IEC 60068-2-1/2
Type Level
Operating range
-10 °C to +55 °C
Storage range
-25 °C to +70 °C
1.4.1.2 Humidity
IEC 60068-2-3
Type Level
Operational test
56 days at 40 °C and 95 % relative humidity
1.4.1.3 Transient Overvoltage
IEC 60255-5
Type Level
Between all M4 terminals and earth, or
between any two independent circuits
5.0 kV, 1.2/50 μs 0.5j
1.4.1.4 Insulation
IEC 60255-5
Type Level
Between any M4 terminal and earth
Between independent circuits
2.5 kV AC RMS for 1 min
Across normally open contacts 1.0 kV AC RMS for 1 min
1.4.1.5 IP Ratings
Type Level
Installed with cover on IP 50 from front
Installed with cover removed IP 30 from front
1.4.2 Emissions
IEC 60255-25
1.4.2.1 Radiated Radio Frequency
Type Limits at 10 m, Quasi-peak
30 to 230 MHz
40 dB(μV/m)
230 to 10000 MHz
47 dB(μV/m)
1.4.2.2 Conducted Radio Frequency
Limits
Type
Quasi-peak Average
0.15 to 0.5 MHz
79 dB(μV) 66 dB(μV)
0.5 to 30 MHz
73 dB(μV) 60 dB(μV)
©2010 Siemens Protection Devices Limited Chapter 3 Page 13 of 49