7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 36 of 76
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table Section 5.2.)
Timeouts while waiting for:
Data Link Confirm: None 7 Fixed at 2sec Variable Configurable.
Complete Appl. Fragment: 7 None Fixed at ____ Variable Configurable
Application Confirm: None 7 Fixed at 10sec Variable Configurable.
Complete Appl. Response: 7 None Fixed at ____ Variable Configurable
Others: Transmission Delay, (0 sec)
Select/Operate Arm Timeout, (5 sec)
Need Time Interval, (30 minutes)
Application File Timeout, (60 sec)
Unsolicited Notification Delay, (5 seconds)
Unsolicited Response Retry Delay, (between 3 – 9 seconds)
Unsolicited Offline Interval, (30 seconds)
Binary Change Event Scan Period, (Polled, Not Applicable)
Double Bit Change Event Scan Period, (Unsupported - Not Applicable)
Analog Change Event Scan Period, (Unsupported - Not Applicable)
Counter Change Event Scan Period, (Unsupported - Not Applicable)
Frozen Counter Change Event Scan Period, (Unsupported - Not Applicable)
String Change Event Scan Period, (Unsupported - Not Applicable)
Virtual Terminal Event Scan Period, (Unsupported - Not Applicable)
Sends/Executes Control Operations:
WRITE Binary Outputs 7 Never Always Sometimes Configurable
SELECT/OPERATE Never 7 Always Sometimes Configurable
DIRECT OPERATE Never 7 Always Sometimes Configurable
DIRECT OPERATE – NO ACK Never 7 Always Sometimes Configurable
Count > 1 7 Never Always Sometimes Configurable
Pulse On Never Always 7 Sometimes Configurable
Pulse Off Never Always 7 Sometimes Configurable
Latch On Never Always 7 Sometimes Configurable
Latch Off Never Always 7 Sometimes Configurable
Queue 7 Never Always Sometimes Configurable
Clear Queue 7 Never Always Sometimes Configurable
Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.
Reports Binary Input Change Events when no
specific variation requested:
Never
Only time-tagged
Only non-time-tagged
7 Configurable to send one or the
other
Reports time-tagged Binary Input Change Events
when no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
7 Configurable
Sends Unsolicited Responses:
Never
7 Configurable
Only certain objects
Sometimes (attach explanation)
7 ENABLE/DISABLE UNSOLICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
7 Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Default Counter Object/Variation:
7 No Counters Reported
Configurable
Default Object
Default Variation:
Point-by-point list attached
Counters Roll Over at:
7 No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value: _____
Point-by-point list attached