7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited Chapter 4 Page 39 of 76
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes
(dec)
Qualifier
Codes (hex)
Function
Codes (dec)
Qualifier
Codes (hex)
10 2
(default –
see note 1)
Binary Output Status
1(read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17,27,28 (index)
129 (response
)
00, 01 (start-stop)
17, 28
(index –
see note 2)
11 0 Binary Output Change – Any
Variation
1(read)
06 (no range, or all)
07, 08 (limited qty)
11 1
(default –
see note 1)
Binary Output Change without
Time
1(read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28
(index )
11 2
Binary Output Change with
Time
1(read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28
(index )
12 0 Control Relay Output Block
22
(assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12 1 Control Relay Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
17, 28 (index) 129
(response)
echo of request
12 2 Pattern Control Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op,
noack)
7 (limited quantity) 129
(response)
echo of request
12 3 Pattern Mask
3 (select)
4 (operate)
5 (direct op)
6 (dir. op,
noack)
00, 01 (start-stop) 129 (response
)
echo of request
30 0 Analog Input - Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response
)
00, 01 (start-stop)
17, 28 (index –
see note 2)

Table of Contents