861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11 141/214
Installation
Bolt the lower rear walls together with the retainers. Use 8 bolts M6x12 for each rear wall.
Tightening torque: 12 Nm.
Fig. 167: Mounting lower rear walls
Bolt the upper rear walls together with the retainers. Use 10 bolts M6x12 for each rear wall.
Tightening torque: 12 Nm.
Fig. 168: Mounting upper rear walls