Installation
86/214 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 861-9601.9
Remove the busbars ④ linked to the twin busbar connection. To do this, remove the four
hexagon nuts M10 with plain washers . Secure the two links against falling down, and
take the three busbars ④ out carefully.
To remove the earthing lug ② , unscrew the two hexagon head bolts M12x30 with plain
washers.
Fig. 88: Removing the busbar
Hexagon nut M10 with plain washer
Link
Twin busbar link (called supporting angle hereafter)
Busbars
Fig. 89: Removing the earthing lug
Busbar housing
(upper row)
Earthing lug
Busbar housing
(lower row)