861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11 91/214
Installation
Use 8 bolt-and-washer assemblies M8 in order to bolt busbar housings located one
beneath the other together (tightening torque: 20 Nm).
Use 8 bolt-and-washer assemblies M8 ① in order to bolt busbar housings located side by
side together (tightening torque: 20 Nm).
Fasten earthing lugs ② to the busbar housings. To do this, use two hexagon head
bolts M12x30 with plain washers (tightening torque: 20 Nm).
Fig. 99: Bolting busbar housings together
Fig. 100: Setup: Completely assembled busbar
Hexagon nut M10 with plain washer
Busbar
Busbar lug
Twin busbar connection

Table of Contents