Project engineering
49
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
4.4 Parameter sets: Wide-spectrum smoke detector
4.4.1 Wide-spectrum smoke detector FDO241
4.4.1.1 Description
Robust (2):
The priority of the 'Robust' parameter set is to a robust response. It is thus
particularly suited for the application in rooms where deceptive phenomena such
as cigarette smoke can be expected.
Universal (1):
With the 'Universal' parameter set the sensitivity and response time are between
'Robust' and 'Sensitive'.
Sensitive (3):
This parameter set is both fast and sensitive. It is thus especially suited for rooms
without deceptive phenomena, where the priority is on possibly early fire detection.
Download 1 (14) / Download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).
4.4.1.2 Application
Risk of injury to
persons
Concentration
of valuable
items
Room
geometry
Deceptive
phenomena
Risk of fire Critical fire size No. Name
small …
large
low…
high
simple…
complex
few…
many
small …
large
small …
medium
2 Robust
1 Universal
3 Sensitive