5.13.2.1 Use of unshielded cables
Guideline
z The connection is established from base to base using twisted or non-twisted
wire pairs.
+
-
+
-
+
-
+
-
+
-
+
-
LINE
+
-
+
-
+
-
+
-
1
2
C
4
B
3
A
+
Connection diagram for collective detector line with and without external alarm indicators
(without shielded cables)
1 Control panel 3 External alarm indicator DJ119x
2 Detector base FDB201/FDB201-AA,
FDB202
4 End-of-line depending on control
panel
Notes
z Standard wiring:
The external alarm indicator is connected to the positive and negative poles of
each detector.
z Wire-saving cabling:
The external alarm indicators are connected as follows:
The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
The external alarm indicator must be connected to the positive pole of every
other detector (B).
The external alarm indicator need not be connected to the negative pole of
each other detector (C).
The wire-saving cabling for external alarm indicators is not admissible for new
installations.