Project engineering
52
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
4.5 Parameter sets: Heat detector
4.5.1 Heat detector FDT241
4.5.1.1 Description
The heat detector FDT241 has the following parameter sets:
z A1R (1)
z BR (2)
z A1S (3)
z BS (4)
z Download 1 (14) / Download 2 (15)
Application-specific parameter sets that can be loaded on site (depending on
the control panel).
Notes on the designations A1 and B
z A1-parameter sets should be applied at an ambient temperature of
approximately 25 ℃. However, they can be applied at temperatures up to 50℃.
The static response temperature is 60°C.
z B-parameter sets are normally applied at temperatures around 40 °C. They can
be applied at temperatures up to 65°C. The static response temperature is
80°C.
Notes on the designations R and S
In comparison to the S-parameter sets, R-parameter sets additionally trigger
alarms in the case of a temperature increase (e.g. from 20 °C to 50 °C within a few
minutes).