Project engineering
51
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
4.4.2 Wide-spectrum smoke detector FDO221
4.4.2.1 Description
Standard (2):
The priority of the 'Standard' parameter set is set to robust response. It is thus
particularly suited to application in rooms where few deceptive phenomena such as
cigarette smoke can be expected.
Standard Plus (3):
This parameter set is both fast and sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.
4.4.2.2 Application
Risk of injury to
persons
Concentration
of valuable
items
Room
geometry
Deceptive
phenomena
Risk of fire Critical fire size No. Name
small …
large
low…
high
simple…
complex
few…
many
small …
large
small …
medium
2 Standard
3 Standard Plus
4.4.2.3 Specification
No. Name Response time [s] Sensitivity [%/m]
2 Standard 60 2.8
3 Standard Plus 50 2
All parameter sets meet the standard EN 54-7.