Project engineering
56
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
4.7 Application examples
Application recommendations such as the selection of the detector type and its
settings for the various applications are described in document 010030 'Fire
detector application guideline'.
The following table includes examples regarding the selection of the detector and
the parameter set. These examples cannot be used universally but serve only as
typical examples.
Environment Detector Parameter set
Normal office room without
any particular deceptive
phenomena
No special requirements
⇨ FDOOT221 or FDO221
Standard
Possible deceptive
phenomena, e.g. electric
kettle
Vapor as deceptive phenomenon
⇨ FDOOT241
Balanced or Suppression
Kitchen A lot of vapor as deceptive phenomenon
⇨ FDOOT241 or FDT241
FDOOT241: Suppression or BS
FDT241: BS
Hospital room, museum Quick response needed, no deceptive
phenomena expected
⇨ FDOOT241 or FDO241
FDOOT241: Fast Response
FDO241: Sensitive
Clean room Fast and very sensitive reaction required
⇨ FDOOT241
High Sensitive