5.12 Cable entry
The detector bases include a spring clip (admissible wire/strand cross-section
0.28... 1.5 mm
2
). Only one wire is allowed to be connected per terminal. This is the
only way in which a faultless connection can be guaranteed.
!
30°
1
3
4
5
6
7
2
Cable entry in detector base
1 The conductor loops must be placed flat in the base
bottom.
5 Contact for test tips
2 The conductor loops must not be placed over this
zone, as otherwise the detector cannot be inserted
correctly.
6 Turn the screwdriver 90° in the direction of the arrow
(left) to only loosen the conductors and insert the strand.
3 Screwless connection terminals 7 Optimum insertion of the wire without tool, at an angle of
approx. 30°
4 Bare length 6.5 ... 7.5 mm