Mounting / Installation
73
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
5.13.2 Connection diagram (collective)
General
z A control-panel specific end-of-line element (EOL) must be connected at the
end of the collective detector line.
Connecting external alarm indicators
The following points must be noted when connecting external alarm indicators:
z If the external alarm indicator is connected to only one detector, there is no
limitation.
z If the external alarm indicator is connected to more than one detector, this is
only admissible on the following conditions:
The detectors are of the FD20 generation (they are not to be mixed with
older detector generations, e.g. AlgoRex detectors)
No sounder base is used
The detectors must have the part number and product version (ES) in
question (see table)
Part number
FDOOT241-9
Product version (ES)
FDOOT241-9
External alarm indicator connected to
several collective detectors
A5Q00004813 < 13
1
not admissible
A5Q00004813 ≥ 30
1
permissible
2
A5Q00015955 13 ≤ ES < 30 permissible
2
1
This also applies to the flame detector FDF2x1-9 and the linear smoke detector
FDL2x1-9
2
The cabling of the external alarm indicators can be migrated to FDnet without
any changes.