8 Specifications
Unless otherwise mentioned, the following data applies:
Temperature = 25°C
Air pressure = 1000 hPa (750 Torr)
8.1 Technical data FDOOT241-x, FDOOT221
8.1.1 General (irrespective of the detector line)
Device characteristics Response sensitivity (typ.):
z FDOOT221 6 … 12 %/m (depending on the
parameter set)
z FDOOT241-x 3 … 12 %/m (depending on the
parameter set)
Compensation speed ≤ 1/45 voltage increase for
detection/h
Detector diagnosis With detector exchanger and tester
FDUD29x
Ambient conditions Permitted ambient temperature:
z FDOOT221 -10 … +60 ℃
z FDOOT241-x -25 … +70 °C
Storage temperature -30 … +75 °C
Air humidity ≤ 95 % rel.
Protection categories according to
EN 60529/IEC 60529:
z Base FDB201/FDB221/
FDB202/FDB222
IP43
z Base attachment FDB291 with base
FDB201/FDB221/
FDB202/FDB222
IP43
z Base attachment humid FDB293 with
base FDB201/FDB221/
FDB202/FDB222:
– FDOOT241-8
– FDOOT241-9
IP54
IP44
z Sounder base FDSB29x IP43
Electromagnetic compatibility:
z 1 MHz … 2 GHz 50 V/m
Permissible wind speed:
z FDOOT221 Max. 5 m/s
z FDOOT241-x Max. 20 m/s