Specifications
87
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Collective maximum current connection factor / Alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Use as Parameter
set no.
Parameter set name Maximum
current
connection
factor for ES
<30
Maximum
current
connection
factor for ES
<30
1
Alarm verification on
control panel
permitted with
detector ES < 13
(verification time at
the control panel
≥ 50 s)
Alarm verification on
control panel
permitted with
detector ES ≥13
(verification time at
the control panel ≥
30 s)
2 Robust
4 Balanced
5 Suppression
2
1,5
No
Yes
6 Fast Response 2 1,5 Yes Yes
7 High Compensation 2 1,5
2
No Yes
0 (ES ≥ 13) High Compensation – 1,25
2
Yes Yes
0 (ES < 13) Insensitive 1,5 – No Yes
8 High Suppression – 1,5 – Yes
Neural fire
detector
(FDOOT)
9 High Sensitive Fast – 1,5 – Yes
0 Universal
1 Universal
2 Robust
2 1,5 No Yes
Wide-spectrum
smoke detector
(FDO)
3 Sensitive 2 1,5 Yes Yes
Heat detector
(FDT)
0 … 4 all parameter sets 2 1,5 No Yes
1
For CS1115 the maximum current connection factor values in the column
apply for ES < 30
2
Different load factors due to the different measuring cycles