Specifications
90
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Device characteristics Response sensitivity:
z FDO221 Typ. 2 ... 3.5 %/m (depending on
the parameter set)
z FDO241 Typ. 1.4 ... 3.5 %/m (depending on
the parameter set)
Compensation, zone 'normal' ≤ 1 voltage increases for detection
Compensation, zone
'Information/Impairment'
≤ 1.5 voltage increases for
detection
Compensation speed ≤ 1/45 voltage increase for
detection/h
Detector diagnosis With detector exchanger and tester
FDUD29x
Ambient conditions Permitted ambient temperature
z FDO221 -10 … +60 ℃
z FDO241 -25 … +70 °C
Storage temperature -30 … +75 °C
Air humidity ≤95 % rel.
Protection categories according to
EN 60529/IEC 60529:
z Base FDB221/FDB222 IP43
z Base attachment FDB291 with base
FDB221/FDB222
IP43
z Base attachment humid FDB293 with
base FDB221/FDB222
IP44
z Sounder base FDSB29x IP43
Electromagnetic compatibility:
z 1 MHz ... 2 GHz 50 V/m
Permissible wind speed Max. 5 m/s
Mechanical data Colour ∼RAL 9010 pure white
Standards Standards EN 54-7, EN 54-17
VdS approvals:
z FDO221 G204018
z FDO241 G204017
LPCB approvals:
z FDO221 126ab/02
z FDO241 126ab/01
FM approvals:
z FDO221 3029351
z FDO241 3029351
Certificates:
z FDO221 0786-CPD-20001
z FDO241 0786-CPD-20002
CE conformity mark Yes
QA Standards Siemens Standard SN 36350